  • <tr id='QcNkd7'><strong id='QcNkd7'></strong><small id='QcNkd7'></small><button id='QcNkd7'></button><li id='QcNkd7'><noscript id='QcNkd7'><big id='QcNkd7'></big><dt id='QcNkd7'></dt></noscript></li></tr><ol id='QcNkd7'><option id='QcNkd7'><table id='QcNkd7'><blockquote id='QcNkd7'><tbody id='QcNkd7'></tbody></blockquote></table></option></ol><u id='QcNkd7'></u><kbd id='QcNkd7'><kbd id='QcNkd7'></kbd></kbd>

    <code id='QcNkd7'><strong id='QcNkd7'></strong></code>

    <fieldset id='QcNkd7'></fieldset>
          <span id='QcNkd7'></span>

              <ins id='QcNkd7'></ins>
              <acronym id='QcNkd7'><em id='QcNkd7'></em><td id='QcNkd7'><div id='QcNkd7'></div></td></acronym><address id='QcNkd7'><big id='QcNkd7'><big id='QcNkd7'></big><legend id='QcNkd7'></legend></big></address>

              <i id='QcNkd7'><div id='QcNkd7'><ins id='QcNkd7'></ins></div></i>
              <i id='QcNkd7'></i>
            1. <dl id='QcNkd7'></dl>
              1. <blockquote id='QcNkd7'><q id='QcNkd7'><noscript id='QcNkd7'></noscript><dt id='QcNkd7'></dt></q></blockquote><noframes id='QcNkd7'><i id='QcNkd7'></i>

                欢迎访问上海静源消声设备工程有限公司官方网站,我们将竭诚为您服务!

                站点地图

                楼宇案例

                上海浦江双辉大厦

                一、 概况
                上海浦江双辉国际大厦是陆家嘴国际金融『区首座“双子楼”,大楼调试时空调系统的噪声传到办公区域的噪声达到53~55 dB(A) ,对办公区域的环境严重影响,为了︽办公区域有个良好的办公环境,我公司受委托对两栋大楼空调机组运行时的噪声拟定治理方案。


                二、 设计范围
                本设计针对大楼空调机组对办公区域环境的影响提出噪声治理方案。


                三、 设计目标
                空调机组运行时办公区域的噪声不大于45dB(A)(扣除背景噪声级的影响)。


                四、 噪声控制措施
                根据设计目标和基本情况,本着有效、经济、合理和可靠的原则,提出如下噪声控制措施:
                因办公区域已经在装修了所以只能在机房内做消声降噪处理。把空调机组送风口处的风管和原有消声弯头拆除,安装一台非标消声静压箱,由于机房内设备已全部安装完毕所以非标消声静压箱只能散件进场现场拼装。


                五、噪声治理◆结果
                采取了以上措施后,在排除其它噪声源干扰的前提下,空调机组运行时每个楼层在办公区域处的噪声都⌒不大于45 dB(A)。



                上一个:
                北京∑ 中国尊
                下一个: